Alarms

An alarm is a condition that needs attention and lasts until something is done about it: a startup configuration that failed to apply, a software slot the bootloader gave up on, a backup that did not run. The device raises an alarm when the condition appears and clears it when the condition goes away. A cleared alarm stays in the list, so what happened while nobody was watching can still be seen, until it is purged.

The alarm list follows RFC 8632 and is served under /ietf-alarms:alarms. A monitoring system reads it over NETCONF or RESTCONF, the WebUI has an Alarms page and shows the active ones on its dashboard, and the fault LED of boards that have one follows it. Alarm changes are logged to syslog.

Note

The alarm list is kept in memory and starts empty at boot. Alarms, and what operators have done with them, do not survive a reboot; a condition that persists raises its alarm again, as new and unacknowledged. Shelves and severity profiles are configuration and stay.

Alarm Types

Alarm type Severity Raised when
startup-config-failed critical The startup configuration could not be applied, the device runs its failure configuration
boot-fallback major A software slot failed to boot and is marked bad, the device runs the other slot
partition-out-of-date warning The other software partition holds an older release than the running one, or none; upgrade refreshes the fallback
link-down major An enabled port, Wi-Fi interface or veth has had no link for ten seconds; disabling it in the configuration clears the alarm, so shelve the ports that have nothing connected
update-available warning The scheduled update check found a newer release; cleared when it is installed or no longer offered
update-check-failed minor The scheduled update check could not read the update source; cleared by the next check that succeeds
update-install-failed major An unattended update failed to install; cleared by the next one that succeeds
external any A script or an external system raised it, see below

The full list the device can raise, with the severity of each, is in the alarm inventory:

curl -k -u admin:admin https://example.local/restconf/data/ietf-alarms:alarms/alarm-inventory

Reading Alarms

The alarm list has one entry per alarm, keyed by what it is about, the resource, and its type. An interface is named by its path in the data model, /ietf-interfaces:interfaces/interface[name='eth7'], so a client can take the alarm straight to the interface; the CLI and the WebUI show the name. Each entry says when it was first raised, when it last changed, its severity, whether it is cleared, and what operators have done with it. In the CLI:

admin@example:/> show alarms
LAST CHANGE       SEVERITY  STATE    RESOURCE   TYPE                TEXT
2026-11-03 06:12  critical  active   backup     external (nightly)  Nightly backup failed
2026-11-03 15:40  minor     closed   sensor3    external            Humidity sensor unreachable
2026-11-03 08:30  major     cleared  disk-full  external            Disk 95% full
1 shelved, see 'show alarms shelved'

A resource shows its alarms in full, text, every timestamp and the operator notes:

admin@example:/> show alarms sensor3
sensor3  external
  Severity    : minor
  State       : closed
  Created     : 2026-11-03T15:40:00+00:00
  Last raised : 2026-11-03T15:40:00+00:00
  Last change : 2026-11-03T15:40:00+00:00
  Text        : Humidity sensor unreachable
  Operator history:
    2026-11-03 15:42  ack     admin
    2026-11-03 15:45  closed  admin  Sensor replaced

The same over RESTCONF:

curl -k -u admin:admin https://example.local/restconf/data/ietf-alarms:alarms/alarm-list
{
  "ietf-alarms:alarm-list": {
    "number-of-alarms": 1,
    "last-changed": "2026-11-03T06:12:40Z",
    "alarm": [
      {
        "resource": "backup",
        "alarm-type-id": "infix-alarms:external",
        "alarm-type-qualifier": "",
        "time-created": "2026-11-03T06:12:40Z",
        "is-cleared": false,
        "last-raised": "2026-11-03T06:12:40Z",
        "last-changed": "2026-11-03T06:12:40Z",
        "perceived-severity": "critical",
        "alarm-text": "Nightly backup failed"
      }
    ]
  }
}

The summary counts alarms per severity, for a dashboard or a quick check:

curl -k -u admin:admin https://example.local/restconf/data/ietf-alarms:alarms/summary

Acknowledging and Closing

The set-operator-state action on an alarm records that someone has seen it, ack, or dealt with it, closed, with an optional note. The history of such changes is kept with the alarm, and goes with it when the alarm is purged or the device reboots. In the CLI, an alarm is named by its resource; the type is only needed when the same resource has alarms of several types:

admin@example:/> alarm ack backup text "Cable ordered"
Alarm backup (external) acknowledged.
admin@example:/> alarm close eth7
Alarm eth7 (link-down) closed.

Over RESTCONF:

curl -k -u admin:admin -X POST \
  -H 'Content-Type: application/yang-data+json' \
  -d '{"ietf-alarms:input": {"state": "ack", "text": "Cable ordered"}}' \
  "https://example.local/restconf/data/ietf-alarms:alarms/alarm-list/alarm=backup,infix-alarms:external,/set-operator-state"

The alarm list has a set-operator-state action of its own for many alarms in one call. It takes the same filter as purging below, the state and an optional note, and answers with how many alarms changed. Shelved alarms and alarms already in that state are left alone. The WebUI's Close all uses it:

curl -k -u admin:admin -X POST \
  -H 'Content-Type: application/yang-data+json' \
  -d '{"infix-alarms:input": {"alarm-clearance-status": "not-cleared", "state": "closed", "text": "Site visit done"}}' \
  https://example.local/restconf/data/ietf-alarms:alarms/alarm-list/infix-alarms:set-operator-state

Purging

Cleared alarms stay in the list until purged. In the CLI, alarm purge removes every cleared alarm, alarm purge all the active ones too:

admin@example:/> alarm purge
Purged 2 alarm(s)

The purge-alarms action behind it also takes a filter: only alarms older than a given age, of a given severity, or in a given operator state. Without a filter it removes every cleared alarm and returns how many went:

curl -k -u admin:admin -X POST \
  -H 'Content-Type: application/yang-data+json' \
  -d '{"ietf-alarms:input": {"alarm-clearance-status": "cleared", "older-than": {"days": 7}}}' \
  https://example.local/restconf/data/ietf-alarms:alarms/alarm-list/purge-alarms

Purging an alarm that is not cleared only forgets it; the condition is not touched, and the alarm returns the next time it changes.

Shelving

A shelf hides alarms that are known and expected, for a resource under repair or a port with nothing connected, without disabling the alarm type. Shelved alarms are kept apart in shelved-alarms, do not count in the summary and do not light the LED. Removing the shelf brings them back.

admin@example:/> configure
admin@example:/config/> edit alarms control shelf spare-ports
admin@example:/config/alarms/control/shelf/spare-ports/> set resource eth[5-8]
admin@example:/config/alarms/control/shelf/spare-ports/> set description "Not patched yet"
admin@example:/config/alarms/control/shelf/spare-ports/> leave

Shelved alarms are listed separately:

admin@example:/> show alarms shelved
LAST CHANGE       SEVERITY  STATE   RESOURCE  TYPE       SHELF        TEXT
2026-11-03 05:00  major     active  eth7      link-down  spare-ports  An enabled interface has no link.

A resource is matched by a regular expression against its whole name, eth7 for an interface, or against the full path. A shelf may also name alarm types, in which case an alarm must match both the resource and the type. The qualifier match is a regular expression too, .* takes every qualifier, including none:

admin@example:/config/alarms/control/shelf/spare-ports/> set alarm-type link-down alarm-type-qualifier-match .*

A shelved alarm takes no operator state. alarm ack and alarm close refuse it until the shelf is removed.

Severity Assignment

The severity of an alarm type can be changed per resource with an alarm profile. A profile is keyed by the alarm type, a qualifier match and a resource match, both regular expressions as in a shelf, and needs a description. To treat a lost link on uplinks as critical:

admin@example:/config/> edit alarms alarm-profile link-down alarm-type-qualifier-match .* resource "eth0|eth1"
admin@example:/config/alarms/alarm-profile/.../> set description "Uplinks"
admin@example:/config/alarms/alarm-profile/.../> set alarm-severity-assignment-profile severity-level critical
admin@example:/config/alarms/alarm-profile/.../> leave

The first profile that matches an alarm applies. A profile with one severity level gives every matching alarm that level. External alarms can be raised at any severity, and a profile with several levels maps them in order, lowest to highest, so a script's alarms can be held to a range of your own. The assigned level shows as the alarm's perceived-severity, and removing the profile puts the original back.

Alarms from Scripts

A script, a container health check, or an external monitoring system can raise alarms of the external type. Over the management protocols, the raise-alarm and clear-alarm operations do it, and in the CLI alarm clear clears one:

admin@example:/> alarm clear backup
curl -k -u admin:admin -X POST \
  -H 'Content-Type: application/yang-data+json' \
  -d '{"infix-alarms:input": {"resource": "backup", "severity": "critical", "text": "Nightly backup failed"}}' \
  https://example.local/restconf/operations/infix-alarms:raise-alarm

On the device itself, an alarm is a file. A script raises one by creating /run/alarm/active/external/<resource> and clears it by removing the file. An empty file is a complete alarm with severity indeterminate; to say more, write a JSON object with severity and text:

echo '{"severity": "major", "text": "Disk 95% full"}' > /run/alarm/active/external/disk-full
...
rm /run/alarm/active/external/disk-full

The resource is one word: letters, digits, ., _, : and -. A qualifier that tells several alarms on the same resource apart is given as <resource>@<qualifier> in the file name, or as the alarm-type-qualifier input of the operations. The directory is writable by members of the wheel group.